With the objective of ensuring the safety of personnel, vehicles utilizing the elevator, and the elevator itself-and taking into account the aforementioned application characteristics of car elevators as well as existing relevant technical standards for elevators-the design, manufacture, installation, and inspection of car elevators shall comply with the following technical requirements (for freight elevators permitted to carry forklifts within the car, the hoistway and guide system shall also be designed and installed in accordance with the technical requirements for car elevators).
1. Markings and Symbols
On the floor surface at each landing door of a car elevator, the direction of travel should be clearly indicated. At the landing door entrance and within the elevator car, signs indicating the maximum permissible dimensions (length, width, and height) and the load limit shall be displayed in conspicuous locations, fabricated from durable materials. The height of the lettering shall be no less than 10 cm and must be highly legible.
2.Hoistway
Requirements for Hoistway Strength
The hoistway structure for car elevators shall possess sufficient strength to withstand not only the loads typically associated with the operation of standard elevators but also the additional loads generated during the loading and unloading of vehicles within the car. For traction-type elevators, the hoistway shall comply with the relevant requirements of GB 7588-2003; it is recommended to construct the hoistway using monolithic reinforced concrete casting, or by forming a reinforced concrete frame with the hoistway walls infilled using high-quality solid bricks. For hydraulic-type elevators, the use of concrete hoistway structures is also recommended; however, for multi-cylinder, side-mounted, direct-acting systems, solid brick hoistway walls may be utilized, provided they meet all applicable requirements. When mounting guide rail brackets to solid brick hoistway walls, through-bolts paired with continuous steel backing plates shall be employed; the surface area of the steel backing plates must extend at least 80 mm beyond the center of the cross-section of each bolt. The bolt holes in the steel backing plates shall not be excessively large. The bolts used shall be Grade 8.8 high-strength bolts with a diameter of no less than 14 mm, and they shall be fitted with flat washers as well as elastic washers or other anti-loosening devices.
Requirements for the Structural Integrity of Hoistway Walls and Landing Door Sills
The hoistway walls adjacent to the landing doors, together with the landing door sills, shall possess sufficient structural integrity and mutual rigidity.
3. Guiding System
The guide rails, along with their accessories and joints, shall be capable of withstanding the various loads and forces imposed upon them during the operation of the elevator, and shall be capable of:
(1) Ensuring the proper guidance of both the elevator car and the counterweight. (2) To counteract the tilting moments exerted on the car during the entry and exit of vehicles, the car guiding system shall utilize no fewer than four rigid, solid steel guide rails. Guide rail deformation must be restricted within a specific range to ensure that: ① Accidental unlocking of the doors does not occur; ② The operation of safety devices remains unimpaired; and ③ Moving components do not collide with other parts.
4. Car
(1) Control panels or other operating devices shall be installed on the car walls adjacent to both the entrance and exit doors. These devices shall be positioned such that the driver inside the passenger vehicle can operate the elevator-specifically to open or close the doors-without having to exit the vehicle.
(2) The car floor shall be constructed from non-slip materials and equipped with vehicle guiding devices and parking lines. These features serve to ensure that vehicles are parked within the designated lines, thereby minimizing the likelihood of the vehicle scraping against the car walls or colliding with the car doors during entry or exit.
(3) To mitigate the inherent risk of overload that may arise when passengers remain inside vehicles while using the car elevator-such as during shift changes at maintenance workshops or during personnel evacuations at supermarkets and shopping malls-the car area shall be reasonably restricted based on relevant standards and the external dimensions of the passenger vehicles. Regarding car area: for traction-type elevators, in accordance with standard GB 7588-2003, the area may be determined based on a standard density of 200 kg/m² and the external dimensions of the passenger vehicles. For hydraulic-type elevators, two scenarios apply:
① For elevators with a rated load capacity of less than 4,000 kg, the car area may be determined based on a standard density of 200 kg/m² and the external dimensions of the passenger vehicles.
② For elevators with a rated load capacity of 4,000 kg or more, the car area shall be determined in accordance with the relevant standards for hydraulic freight elevators. When the rated load capacity exceeds 1,600 kg, the car area shall be increased by 0.4 m² for every additional 100 kg of load capacity; this applies specifically to the hydraulic car elevators marked with an asterisk (*) in Table 3. Such elevators may also be utilized as freight elevators.
Regarding car dimensions: the width of the elevator car shall be no less than the vehicle width plus 500 mm; the height shall be no less than the vehicle height plus 100 mm; and the length shall be no less than the vehicle length plus approximately 1 meter. For car elevators dedicated to specific vehicle models-such as those found in automobile manufacturing plants or authorized dealerships (4S stores)-the dimensions and floor area of the car may be smaller than the values specified in Table 2.
(4) For elevators with a car floor area exceeding the prescribed limits, a static load test and a safety gear test-conducted at 150% of the rated load-must be performed prior to commissioning following installation. Accordingly, the power output, traction conditions, rope groove pressure, and other parameters of the car elevator must fully comply with the requirements of relevant standards and regulations.
5. Overload and Off-center Load Protection
The weighing device in a car elevator must not only provide overload protection but also accurately reflect the elevator's load status when the load within the car is off-center (unevenly distributed), thereby enabling users to adjust the load distribution in a timely manner and optimize the elevator's traction conditions. Given that car elevator cars are typically long and narrow, relying solely on a single microswitch or weight sensor mounted on the car's bottom beam-as is common in standard passenger elevators-will fail to accurately reflect the actual load distribution within the car when an off-center load is present.
For traction-type car elevators and center-direct-acting hydraulic elevators, it is recommended to install weight sensors at each of the four corners of the car floor, or to employ alternative methods capable of detecting and indicating off-center loads.
6. Requirements for Access Passages at Landing Entrances
The access passage at the landing entrance of a car elevator must be designed to safely accommodate the entry and exit of a passenger vehicle. The curvature and gradient of the passage must be reasonable, allowing the driver-while seated inside the vehicle-to maintain a clear line of sight of the approach/exit lane extending a distance of at least one car length beyond the elevator entrance. If these visibility requirements cannot be met, supplementary facilities such as mirrors or video monitors must be installed. The design and configuration of these access passages must comply with the relevant provisions of JGJ100-1993, *Code for Design of Automobile Garages*.
7. Prevention of Mixed Occupancy (Vehicles and Pedestrians)
Car elevators must incorporate appropriate measures to prevent the simultaneous occupancy of the elevator car by both vehicles and non-driving personnel, thereby eliminating the safety hazards associated with such mixed usage. 8. Standards Applicable to Other Technical Aspects
Other technical specifications for traction-type car elevators shall comply with the requirements of GB 7588–2003, *Safety Rules for the Construction and Installation of Lifts and Escalators*. Other technical specifications for hydraulic car elevators shall comply with JG 5071–1996, *Hydraulic Lifts*, and GB 21240–2007, *Safety Rules for the Construction and Installation of Hydraulic Lifts*.